SANS1507-4 standard PVC Insulated LV Power Cable

SANS1507-4 standard PVC Insulated LV Power Cable

Specifications:

    For fixed installation of the transmission and distribution systems, tunnels and pipelines and other occasions.

    For situation not supposed to bear external mechanical force.

Quick Detail

Parameter Table

Product Tags

Application :

For fixed installation of the transmission and distribution systems, tunnels and pipelines and other occasions.
For situation not supposed to bear external mechanical force.
Direct burial in free-draining soil conditions for fixed indoor and outdoor installations.
SWA armour and stable water resistant jacket makes them suitable for use inside and outside buildings or for direct burial in the ground.

Construction:

Conductor: Conductor: class 1 solid , class 2 stranded copper conductor or aluminium conductor
Insulation: Polyvinyl Chloride (PVC)
Armour method: Unarmored or Steel Wire Armour (SWA), Steel Tape Armour (STA), Aluminium Wire Armour (AWA), Aluminium Tape Armour (ATA), Steel Wire Armour+Tinned copper wire (SWA+ECC)
Sheath: Polyvinyl Chloride PVC

Standards:

SANS1507-3
Flame Retardant according to IEC/EN 60332-1-2

Properties:

Voltage Rating: 600/1000V
Temperature Range : -10°C to 70°C
Sheath colours: black
Core colours: 2 core -Black and Red
3 core -Red, Yellow and Blue
4 core -Red, Yellow, Blue and Black

Single core power cable (pvc insulated) parameter

Cross-sectional area (mm²) No.&diameter of wire (N/mm) Average overall diameter (mm) Reference weight (kg/km) Conductor resistance (Ω/km) 20℃ Max
1.5 1/1.38 5.8 28 12.1
2.5 1/1.76 6.2 31 7.41
4.0 7/0.85 7.4 38 4.61
6.0 7/1.04 7.9 42 3.08
10 7/1.35 8.9 48 1.83
16 7/1.7 9.4 55 1.15
25 7/2.14 11.4 66 0.727
35 19/1.53 12.9 74 0.524
50 19/1.78 14.5 84 0.387
70 19/2.14 16.5 103 0.268
95 19/2.52 19 129 0.193
120 37/2.03 20.8 151 0.153
150 37/2.25 22.8 167 0.124
185 37/2.52 25.3 197 0.0991
240 61/2.25 28.5 235 0.0754
300 61/2.52 31.5 275 0.0601
400 91/2.36 35.4 326 0.0470
500 91/2.65 39.2 399 0.0366

Two cores power cable (pvc insulated) parameter

Cross-sectional area (mm²) No.&diameter of wire (N/mm) Average overall diameter (mm) Reference weight (kg/km) Conductor resistance (Ω/km) 20℃ Max
2×1.5 1/1.38 12 186 12.1
2×2.5 1/1.76 12.8 225 7.41
2×4.0 7/0.85 15.2 324 4.61
2×6.0 7/1.04 16.2 390 3.08
2×10 7/1.35 18.2 531 1.83
2×16 7/1.7 20.0 699 1.15
2×25 10/1.83 17.2 679 0.727
2×35 14/1.83 18.8 887 0.524
2×50 19/1.83 21.5 1197 0.387
2×70 27/1.83 23.8 1606 0.268
2×95 37/1.83 27.4 2157 0.193
2×120 30/2.32 29.3 2689 0.153
2×150 37/2.32 32.4 3291 0.124
2×185 37/2.52 35.7 4002 0.0991
2×240 48/2.52 40.3 5122 0.0754
2×300 61/2.52 44.5 6430 0.0601
2×400 61/2.95 50.1 8634 0.0470

Three cores power cable (pvc insulated) parameter

Cross-sectional area (mm²) No.& diameter of wire (N/mm) Average overall diameter (mm) Reference weight (kg/km) Conductor resistance (Ω/km) 20℃ Max
3×1.5 1/1.38 12.5 211 12.1
3×2.5 1/1.76 13.3 258 7.41
3×4.0 7/0.85 15.9 379 4.61
3×6.0 7/1.04 17.0 466 3.08
3×10 7/1.35 19.1 646 1.83
3×16 7/1.7 21.3 881 1.15
3×25 10/1.83 19.8 973 0.727
3×35 14/1.83 21.6 1280 0.524
3×50 19/1.83 24.8 1735 0.387
3×70 27/1.83 28.2 2360 0.268
3×95 37/1.83 32.0 3183 0.193
3×120 30/2.32 35.1 3979 0.153
3×150 37/2.32 38.5 4864 0.124
3×185 37/2.52 42.2 5917 0.0991
3×240 48/2.52 48.0 7598 0.0754
3×300 61/2.52 53.3 9548 0.0601
3×400 61/2.95 60.2 12822 0.0470

Four cores power cable (pvc insulated) parameter

Cross-sectional area (mm²) No.&diameter of wire (N/mm) Average overall diameter (mm) Reference weight (kg/km) Conductor resistance (Ω/km) 20℃ Max
4×1.5 1/1.38 13.2 243 12.1
4×2.5 1/1.76 14.2 305 7.41
4×4.0 7/0.85 17.1 454 4.61
4×6.0 7/1.04 18.3 564 3.08
4×10 7/1.35 20.7 794 1.83
4×16 7/1.7 23.1 1095 1.15
4×25 10/1.83 22.1 1270 0.727
4×35 14/1.83 24.3 1677 0.524
4×50 19/1.83 27.7 2274 0.387
4×70 27/1.83 31.7 3113 0.268
4×95 37/1.83 36.8 4207 0.193
4×120 30/2.32 40.1 5259 0.153
4×150 37/2.32 44.4 6446 0.124
4×185 37/2.52 48.5 7846 0.0991
4×240 48/2.52 55.7 10108 0.0754
4×300 61/2.52 61.4 12669 0.0601
4×400 61/2.95 69.0 17049 0.0470

Four Cores power cable (PVC Insulated+SWA) parameter

Size Conductor Insulation Wrapping tape Inner sheath Armour Sheath
Single wire Shape height PVC Non-woven PVC Galvanized steel wire UV-ZRC-PVC
No. Dia. Thickness min. Shape height Layer Thickness Dia. Thickness min. Dia. Dia. No. Dia. Thickness min. Dia.
4×25 7 2.14 5.99 1.2 0.98 8.39 2 0.2 18.78 1.2 0.92 21.18 1.6 40±2 24.38 1.7 1.16 27.78
4×35 7 2.52 7.06 1.2 0.98 9.46 2 0.2 20.95 1.2 0.92 23.35 1.6 44±2 26.55 1.8 1.24 30.15
4×50 10 2.52 8.22 1.4 1.16 11.02 2 0.2 24.27 1.4 1.09 27.07 2.0 42±2 31.07 2.0 1.40 35.07
4×70 14 2.52 9.9 1.4 1.16 12.7 2 0.2 27.65 1.4 1.09 30.45 2.0 47±2 34.45 2.2 1.56 38.85
4×95 19 2.52 11.65 1.6 1.34 14.85 2 0.2 32.16 1.4 1.09 34.96 2.5 43±2 39.96 2.4 1.72 44.76
4×120 24 2.52 13.12 1.6 1.34 16.32 2 0.2 35.14 1.6 1.26 38.34 2.5 47±2 43.34 2.4 1.72 48.14
4×150 30 2.52 14.54 1.8 1.52 18.14 2 0.2 38.97 1.6 1.26 42.17 2.5 52±2 47.17 2.6 1.88 52.37
4×185 37 2.52 16.3 2.0 1.70 20.3 2 0.2 43.51 1.6 1.26 46.71 2.5 57±2 51.71 2.6 1.88 56.91
4×240 37 2.88 18.67 2.2 1.88 23.07 2 0.2 49.27 1.6 1.26 52.47 2.5 64±2 57.47 3.0 2.20 63.47