SANS 1713 Standard MV ABC Aerial Bundled Cable

SANS 1713 Standard MV ABC Aerial Bundled Cable

Specifications:

    SANS 1713— Electric cables -Medium voltage aerial bundled conductors for voltages from 3.8/6.6 kV to 19/33 kV

Quick Detail

Parameter Table

Product Tags

Application:

Suitable for aerial installation and for public power distribution networks

asd
asd

Standard:

SANS 1713--- Electric cables -Medium voltage aerial bundled conductors for voltages from 3,8/6,6 kV to 19/33 kV

Voltage:

6.6kV-22kV

Construction:

Conductor: Aluminum, circular stranded and compacted.
Conductor Screening: Extruded thermosetting semi-conductor layer.
Insulation: XLPE thermosetting material.
Insulation Screening: Semi conducting screen: Extruded thermosetting semi-conducting layer, applied under a swellable semi-conducting tape for watertightness.
Metal screen: Plain soft copper wire and / or copper tape applied helically, or aluminum tape applied longitudinally bonded to the outer PE sheath.
Outer sheath: Extruded black PE sheath, or PVC upon specific customer requirements.
Steel Messenger: 50 or 70 mm² galvanized steel stranded wires, covered with black PE, or PVC upon specific customer requirements.

Why Choose Us?

We produce quality cables by using high-end material:

Why Choose Us (2)
Why Choose Us (3)
Why Choose Us (1)
Why Choose Us (5)
Why Choose Us (4)
Why Choose Us (6)

Rich experience team knowing what's your demand:

1212

Plant with good facilities and capacity to guarantee on-time delivery:

1213

PHASE CORE
Conductor Size mm² nom 35 50 70 95 120 150 185
Conductor Diameter mm app. 7.15 8.25 9.95 11.80 13.10 14.80 15.95
Insulation Diameter mm app. 15.4 16.5 18.2 20.1 21.4 22.7 24.2
Core Sheath Diameter mm app. 20.5 21.6 23.5 25.5 26.8 28.1 29.9
SUPPORT CORE
Conductor Size mm² nom 50 50 50 50 70 70 70
Conductor Diameter mm app. 9.00 9.00 9.00 9.00 10.80 10.80 10.80
Insulation Diameter mm app. 11.5 11.5 11.5 11.5 13.3 13.3 13.3
Maximum Tensile Strength and Pulling Force of Catenary kN 26 26 26 26 37 37 37