IEC/BS Standard 6-10kV-XLPE Insulated MV Middle Voltage Power Cable

IEC/BS Standard 6-10kV-XLPE Insulated MV Middle Voltage Power Cable

Specifications:

    Suitable for energy networks such as power stations. For installation in ducts, underground and outdoor.

    The aluminium wire armour (AWA) for single core cables and steel wire armour (SWA) for multicore cables provide robust mechanical protection making these 11kV cables suitable for direct burial in the ground. These armoured MV mains power cables are more commonly supplied with copper conductors but they are also available with aluminium conductors upon request to the same standard. The copper conductors are stranded (Class 2) whereas the aluminium conductors are compliant to the standard using both stranded and solid (Class 1) constructions.

Quick Detail

Parameter Table

Product Tags

Application :

SThe aluminium wire armour (AWA) for single core cables and steel wire armour (SWA) for multicore cables provide robust mechanical protection making these 11kV cables suitable for direct burial in the ground. These armoured MV mains power cables are more commonly supplied with copper conductors but they are also available with aluminium conductors upon request to the same standard. The copper conductors are stranded (Class 2) whereas the aluminium conductors are compliant to the standard using both stranded and solid (Class 1) constructions.

Standards:

BS6622
IEC 60502

Characteristics :

Conductor: stranded plain annealed circular compacted copper conductors or aluminium conductor
Insulation: cross link polyethylene (XLPE)
Metallic Screen: individual or overall copper tape screen
Separator: copper tape with 10% overlap
Bedding: polyvinyl chloride (PVC)
Armouring: Steel Wire Armour (SWA), Steel Tape Armour (STA), Aluminium Wire Armour (AWA), Aluminium Tape Armour (ATA)
Sheath: PVC outer sheath
Sheath colour: Red or Black

Construction :

1.Conductor
Compact circular stranded copper conductor complying with BS6360 Class 2.
Conductor Screen
Extruded semi-conducting compound bonded to the insulation and applied in the same operation as the insulation.
2.Insulation
Extruded cross-linked ployethylene (XLPE) suitable for operation at a conductor temperature of 90°C.
3.Insulation Screen
Extruded semi-conducting compound applied in the same operation as the insulation. Cold strippable screens are supplied as a standard but fully bonded screens may be provided if specified.
4.Metallic Screen
Copper tapes applied overlapped to provide an earth fault current path.
5.Laying Up
Three cores laid up with polypropylene string fillers to form a compact circular cable, and bound with tape.
6.Tape Binder
7.Sheath
Extruded black polyvinyl chloride (PVC) or Low Smoke Zero Halogen (LSOH) compound is supplied as standard. Alternative materials may be provided if specified.
8.Armouring
Single layer of galvanised circular steel wires.
9.Oversheath
Extruded black polyvinyl chloride (PVC) or Low Smoke Zero Halogen (LSOH) compound is supplied as standard. Alternative materials may be provided if specified e.g medium density polyethylene (MDPE).

Electrical data:

Maximum conductor operating temperature: 90°C
Maximum screen operating temperature: 80°C
Maximum conductor temperature during S.C: 250°C

Current Ratings Conditions:

Ground Temperature 15°C
Ambient temperature (air) 25°C
Depth of burial 0.8m
Thermal resistance of soil 1.2°C m/W

Single-core -6/10 kV

Nominal area conductor Conductor diameter Insulation thickness Nominal overall diameter d Maximum overall diameter Approximate cable weight kg/km Minimum bending radius
mm2 mm mm mm mm Cu Al mm
1x 10 3.8 3.4 17.7 18.7 403 341 262
1x 16 4.7 3.4 19.5 20.6 581 482 289
1x 25 5.9 3.4 21.0 22.2 664 509 315
1x 35 7.0 3.4 22.8 23.8 819 602 330
1x 50 8.2 3.4 24.0 25.0 993 678 350
1x 70 9.9 3.4 25.7 26.7 1237 796 370
1x 95 11.5 3.4 27.3 28.3 1506 908 390
1×120 12.9 3.4 29.0 30.0 1798 1043 420
1×150 14.2 3.4 30.3 31.3 2113 1168 440
1×185 16.2 3.4 32.5 33.5 2508 1343 470
1×240 18.2 3.4 34.7 35.7 3088 1577 500
1×300 21.2 3.4 37.9 38.9 3802 1913 540
1×400 23.4 3.4 40.3 41.3 4806 2286 580
1×500 27.3 3.4 44.4 45.4 5871 2722 630
1×630 30.5 3.4 47.8 48.8 7187 3220 680

Three-cores-6/10 kV

Nominal area conductor Conductor diameter Insulation thickness Nominal overall diameter Maximum overall diameter Approximate cable weight kg/km Minimum bending radius
mm2 mm mm mm mm Cu Al mm
3x 10 3.8 3.4 34.7 35.7 1088 902 500
3x 16 4.7 3.4 37.2 38.2 1981 1683 535
3x 25 5.9 3.4 37.7 38.7 2058 1893 542
3x 35 7.0 3.4 45.2 46.2 3106 2456 640
3x 50 8.2 3.4 47.9 48.9 3739 2795 680
3x 70 9.9 3.4 51.8 52.8 4614 3292 740
3x 95 11.5 3.4 55.5 56.5 5611 3817 790
3×120 12.9 3.4 58.9 59.9 6620 4353 840
3×150 14.2 3.4 61.9 62.9 7722 4887 880
3×185 16.2 3.4 66.4 67.4 9115 5620 940
3×240 18.2 3.4 71.1 72.1 11108 6574 1010

Armoured three-cores-6/10 kV

Nominal area conductor Conductor diameter Insulation thickness Nominal overall diameter Maximum overall diameter Approximate cable weight kg/km Minimum bending radius
mm2 mm mm mm mm Cu Al mm
3x 10 3.8 3.4 38.0 39.1 1580 1394 547
3x 16 4.7 3.4 39.8 40.9 2876 2578 573
3x 25 5.9 3.4 45.2 46.3 3529 3064 648
3x 35 7.0 3.4 50.4 51.4 4358 3707 720
3x 50 8.2 3.4 53.1 54.1 5079 4135 760
3x 70 9.9 3.4 57.0 58.0 6055 4732 810
3x 95 11.5 3.4 60.7 61.7 7151 5356 860
3×120 12.9 3.4 63.9 64.9 8222 5955 910
3×150 14.2 3.4 66.9 67.9 9416 6582 950
3×185 16.2 3.4 71.6 72.6 10979 7484 1020
3×240 18.2 3.4 76.1 77.1 13042 8508 1080